Comparison Chart (UP55A/UP35A, UM33A)


UP55A UP35A UM33A
Model
UP55A
UP35A
UM33A
Size 1/4 DIN  
1/8 DIN    
Depth from the panel surface (mm) 65 65 65
Control Scan Period (msec) Choice 100/200 200 Choice 50/100/200
Display Function Number of PV Display Digits 5 5 5
Active Color PV Display Function
Guide Scroll Display Function
Message Display Function
Bar graph display (Number) (2) (1)  
PV Input Indication Accuracy (% of F.S.) 0.1 0.1 0.1
PV Input Type TC
RTD (3-wire)
RTD (4-wire)    
mV, V
mA
Number of Analog Inputs Standard (Maximum) 1(4) 1 1
Number of SPs (PIDs) Fixed 8 4  
Number of Control Modes Maximum 5 1  
Number of Control Types Maximum 4 4  
Control Output Type Relay Contact Output, Voltage pulse output, Current output  
Algorithm ON/OFF  
PID
(Continuance, Time Proportion)
 
Position proportional  
Heating/cooling  
Number of Analog Outputs Standard (Maximum) 2 (3) 2 1
Number of Digital Inputs Standard (Maximum) 8 (9) 3 (8) 2
Number of Program Patterns Standard (Maximum) 30 2 (4)  
Number of Programs
Number of Segments per
Pattern
Standard (Maximum) 300
99
20 (40)
20 (40)
 
Number of PV Events (Per segment) 8 2  
Number of Time Events (Per segment) 16 4  
Number of Alarms Maximum 8 2 8
Number of Digital Outputs Standard (Maximum) 8 (18) 3 (8) 3 (9)
Communication RS-485 communication (Maximum) (2) (1) (1)
Ethernet communication  
Open Network
(CC-Link/PROFIBUS-DP/DeviceNet)
 
Various Function Quick Setting Function
Split Computation Output Function  
Ratio and Square Root Extraction Function   *3
Remote SP Function  
24 V DC Loop Power Supply Function *2 *2
Heater Break Alarm Function
(Standard type)

(Standard type)
 
Ladder Sequence Function (Number of max. steps) (500) (300)  
Other Specifications Power
Supply
AC100V to 240V
AC/DC 24V
Dust and waterproof Level of Front Panel NEMA4 *1 (IP56) NEMA4 *1 (IP56) NEMA4 *1 (IP56)
Configuration
Tool
Via Light-loader Communication
Via Maintenance Port
Communication
Via RS485/Ethernet communication /
/ /-

The table above includes specifications of the standard models only.
* 1: Hose down test only.
* 2: This function is available when the /L4 or /LC4 option is specified with the detailed code model.
* 3: Square root extraction available